About Composite

Composite

Product Overview

  • Application: Condensate, High Temperature Hot Water, Steam
  • Service Pipe: Carbon Steel, Stainless Steel
  • Temp: Up to 400掳F (204掳C)
  • Nom Length: 20 Ft. 鈥 40 Ft.

System Specifications

Pipe Size Nominal Inner Insulation Thickness Nominal Outer Insulation Thickness HDPE Jacket O.D. System Temperature
2鈥 1陆鈥 1.00鈥 8.00鈥 353掳贵
2陆鈥 2.00鈥 1.00鈥 10.00鈥 353掳贵
3鈥 2.00鈥 1.00鈥 10.00鈥 353掳贵
4鈥 2.50鈥 1.00鈥 12.43鈥 353掳贵
6鈥 2.50鈥 1.00鈥 14.06鈥 353掳贵
8鈥 2.50鈥 1.50鈥 17.83鈥 353掳贵
10鈥 3.00鈥 1.50鈥 19.80鈥 353掳贵
12鈥 3.00鈥 1.50鈥 22.17鈥 353掳贵

Product Description

Service Pipe: Carbon steel service pipe shall be standard weight A53 ERW or A106 seamless beveled for welding. Condensate return piping shall be Schedule 80. All joints for pipe 2陆鈥 and larger in size shall be butt-welded. Sizes 2鈥 and smaller shall be socket welded. Straight lengths of piping will be supplied with 6鈥 of piping exposed at each end for field joint fabrication. Where possible, piping lengths shall be supplied in 40 Ft. random lengths.

Insulation (Inner Layer): The inner layer of insulation will consist of cellular glass, calcium silicate, or perlite.

Insulation (Outer Layer): The outer conduit insulation shall be polyurethane foam with a minimum 1-inch thickness. The polyurethane foam shall have a minimum density of 2.0, and a closed-cell content of 90% to 95% per ASTM D-2856, and shall have a 鈥淜鈥 factor of .14 per ASTM C-177 @ 75掳F.

Exterior Casing: The exterior casing shall be seamless, extruded High-Density Polyethylene (H.D.P.E.) ASTM-1248, with the following physical properties:

  • ASTM D-3350 Resin Type III, Grade P34
  • ASTM D-638 Ultimate Elongation 850%
  • ASTM D-638 Tensile Yield Strength 3300 psi
  • ASTM D-790 Tangent Flexural Modules 175,000 psi

No polyethylene tape casings will be allowed.

Sub-Assemblies: All fittings, anchors, and end seals shall be factory fabricated and insulated. No field fabrication of fittings, anchors, or end seals will be allowed.

Field Joints: After welding and hydrostatic testing, all field joints shall be insulated with insulation materials as supplied by Tricon Piping Systems, Inc.

Expansion Compensation: Expansion and contraction within the piping system shall be accommodated with factory-fabricated oversized elbows, z-bends, and loops.

Installation: Trenches shall be maintained dry until final field closure is complete. Piping system not suitable for use in a high water table. The installing contractor shall handle the piping system in accordance with the directions furnished by the manufacturer and as approved by the architect and engineer. The service piping shall be hydrostatically tested to 1-1/2 times the operating pressure, or as specified in the contract documents. The test shall be maintained for a minimum time of 1 hour. EXERCISE DUE CARE WHEN INSTALLING AND TESTING THE PIPING SYSTEM.

Backfill: A 4-inch layer of sand or fine gravel shall be placed and tamped in the trench to provide stable and uniform bedding for the piping system. Once the system is in place, the trenches shall be carefully backfilled and hand tamped in 6鈥 layers until a cover of at least 24鈥 from the top of the pipe has been achieved. The first 12鈥 of backfill shall be sand or fine gravel less than 陆鈥 in diameter. The remainder of the backfill shall be void of rocks, frozen earth, and foreign material over 6鈥 in diameter. The trench shall be compacted to comply with H-20 Highway loading.

Accessories:

  • Heat Tracing

System Options:

  • *Insulation thickness will vary depending on the type of insulation specified and the operating temperature.
  • **Optional metallic casings for above-ground applications include Spiral Lockseam in Galvanized, Aluminum, or Stainless Steel.
  • **Optional non-metallic casings for below grade offered include Filament Wound FRP.

News

News
Preview Summary Date URL
Tricon Composite Pipe System Tricon Composite Pipe System
For condensate, high temp. hot water, steam up to 400掳F (204掳C). Carbon steel service pipe shall be standard weight A53 ERW or A106 seamless beveled for welding. Condensate return piping shall be Schedule 80. All joints for pipe 2 陆鈥 and larger in size...
Jan 31, 2025

Request for Information / Request a Catalog from Tricon Force Piping Solutions LLC about Composite
 
(Please check companies and/or products above.)
 
*Name:    
*Email:    
Company:    
*Type:    
Phone:    
*Address:    
*Request:    
    (* = Mandatory field) 
Please add me to the mailing list for the free monthly e-Newsletter AECnews.  
     


News archive:
Tricon Composite Pipe System (Jul 28, 2023)
Tricon Composite (Jun 02, 2017)
Tricon Composite (Jan 11, 2016)
Featured Product: Tricon Composite (Feb 08, 2014)