4CID/4FID/4PID. CSI 3-Part Specifications.

jmlogo.jpg (11366 bytes)

SBS Modified Bitumen Specifications

Specification 4CID/4FID/4PID


Four Ply Hot Mopped Modified Bitumen Mineral Surfaced Roofing System. For use over JM insulation, approved decks, or other approved insulations on inclines up to 3" per foot (250 mm/m).

For Regions 1, 2 and 3

Materials per 100 sq. ft. (9.3 m2 ) of Roof Area


Primer (If required):
JM Concrete Primer

1 gallon (3.8 liters)


Intermediate Felts:
GlasPly Premier or GlasPly IV

3 layers


Cap:

4°ä±õ¶Ù�

DynaKap, DynaKap FR, DynaMax or DynaMax FR

4¹ó±õ¶Ù�

DynaGlas, DynaGlas FR or DynaGlas 30 FR

4±Ê±õ¶Ù�

DynaLastic 180, DynaLastic 180 FR, DynaLastic 250 or DynaLastic 250 FR

1 layer


Asphalt (Refer to Para. 7A.8): Trumbull or other JM Approved Asphalt

Incline per foot
Up to 1/2"
1/2" to 3"

Asphalt
190°F, Type III, Steep
220°F, Type IV, Special Steep

Total Weight
92 lbs. (42 kg)
92 lbs. (42 kg)


Approximate installed weight: 175 - 285 lbs. (79 - 129 kg).

General

This specification is for use over any type of approved structural deck which is not nailable and which provides a suitable surface to receive the roof. Poured and pre-cast concrete decks require priming with JM Concrete Primer prior to application of hot asphalt.

This specification is also for use over JM roof insulations, or other approved roof insulations which are not nailable and which provide a suitable surface to receive the roof. Specific written approval is required for any roof insulation that is not supplied by JM. Insulation should be installed in accordance with the appropriate JM Insulation Specification detailed in the JM Commercial/ Industrial Roofing Systems Manual. This specification can also be used in certain reroofing situations. Refer to the "Reroofing" section of the JM Commercial/Industrial Roofing Systems Manual. This specification is not to be used directly over gypsum, either poured or pre-cast, or lightweight, insulating concrete decks or fills.

Design and installation of the deck and/or roof substrate must result in the roof draining freely, to outlets numerous enough   and so located as to remove water promptly and completely. Areas where water ponds for more than 24 hours are unacceptable and will not be eligible for a JM Roofing System Guarantee.

Note: All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual shall be considered part of this specification.