5GNS. CSI 3-Part Specifications. Large file (>500kB).
![]() |
Built-Up Roofing Specifications |
Specification 5GNS. |
For Regions 1, 2 and 3
This specification is for use over any type of approved structural deck
(without insulation) which can receive and adequately retain nails or other types of mechanical fasteners that may be recommended by the deck manufacturer. Examples of such decks are wood and plywood. This specification is not for use directly over lightweight, insulating concrete decks.Design and installation of the deck and/or substrate must result in the
roof draining freely and to outlets numerous enough and so located as to remove water promptly and completely. Areas where water ponds for more than 24 hours are unacceptable and are not eligible to receive a JM Roofing Systems Guarantee.Note: All general instructions contained in the current JM Commercial/Industrial Roofing Systems Manual should be considered part of this
specification. FlashingsFlashing details can be found in the "Bituminous Flashings" section of the
JM Commercial/Industrial Roofing Systems Manual. ApplicationOver wood board decks, one ply of sheathing paper must be used under
the base felt and on top of the wood board deck.Note: On roof decks with slopes up to 2" per foot (166.6 mm/m), the roofing
felts may be installed either perpendicular or parallel to the roof incline. On slopes over 2" per foot (166.6 mm/m), refer to Paragraph 6.11 of this section for special requirements.Using GlasPly Premier or GlasPly IV, apply a piece 9" (229 mm) wide, then
over that, one 18" (457 mm) wide, then over that, one 27" (686 mm) wide. Over these 3 partial sheets, install a full width 36" (914 mm) piece. The following felts are to be applied full width, overlapping the preceding felts by 27 �" (699