Excel 10 W7750A, B Constant Volume AHU Controller. CSI 3-Part Specifications.
Excel 10 |
|
SPECIFICATION DATA |
GENERAL
The W7750A,B is the Constant Volume Air Handling Unit (CVAHU) Controller in the Excel 10 product line family. The CVAHU is a LonMark®
compliant device designed to control single zone and heat pump air handlers.
FEATURES
- Controls single zone and heat pump Air Handling Unit.
- Uses Echelon® LonWorks® network (E-Bus) communications protocol.
- High-speed 78 kilobit communications network.
- Conforms with Echelon® LonMark® HVAC Interoperability standard for Roof Top Unit controllers (profile number 8030).
- Free Topology Transceiver (FTT) network technology is insensitive to polarity, simplifying installation.
- Capable of stand-alone operation and has enhanced features available when using the E-Bus network communications.
- 120 controllers per Q7750A Excel 10 Zone Manager.
- Designed for both staged heating/cooling control and modulating heating/cooling control.
- Uses either Series 60 Floating Control (W7750A and B) or PWM (W7750B only) providing modulating control for heating/cooling equipment.
- Supports two types of economizer control, modulating control and enable/disable control.
- Provides Proportional Integral Derivative (PID) temperature control.
- Uses an adaptive algorithm (patent pending) that continuously adjusts the discharge air setpoint as needed.
- Factory configured via EEPROM with critical user parameter default values.
- Motion sensor interface for enhanced energy savings.
- Window sensor input for additional energy savings.
DESCRIPTION
The W7750A,B is the Constant Volume Air Handling Unit (CVAHU) Controller in the Excel 10 product line family. The CVAHU is a LonMark®
compliant device designed to control single zone and heat pump air handlers.
Control Techniques Supported (Heating and Cooling):
Output capacity:
W7750A� Six digital outputs
W7750B� Eight digital outputs
� Heat pump control: Up to four compressors and up to four stages of auxiliary heat.
� Up to four stages of electric or gas fired heating.
� Up to four stages of mechanical cooling.
� Floating hot water or steam heat.
� Pulse width modulated heat (W7750B only).
� Floating chilled water cooling.
� Pulse width modulating cooling (W7750B only).
� Floating mixed air damper output.
� Pulse width modulating mixed air damper output, (W7750B only).
� Occupancy sensor override and window open override.
SPECIFICATIONS
Models: W7750A,B
The W7750 is field mounted at or near the Air Handling Uni