Steel Aboveground Oil/Water Separator Single or Double Wall. CSI 3-Part Specifications.
SPECIFICATIONS
STEEL ABOVEGROUND OIL/WATER SEPARATOR SINGLE-WALL OR DOUBLE WALL
SECTION 02700
DRAINAGE
PART 1: GENERAL
1.01 Related Documents
1. The provisions of the General Conditions, Supplementary Conditions, Sections included under Division 1, General Requirements, and Section ______ of this Division are included as part of this Section as though bound herein.
2. Refer to details and schedules on the drawings for additional requirements.
1.02 Related Work
1. Drop-out box: Contractor to furnish and install precast, steel, or fiberglass drop-out box.
2. Plastic pipe: Contractor to furnish and install all necessary PVC drainage pipe and fittings.
Contractor shall install one butterfly valve between the drop-out box and tank inlet, as well as on the effluent pipe.
1.03 Description/Summary
1. The Contractor shall furnish the labor, materials, equipment, appliances, services and hauling, and perform operations in connection with the construction and installation of the separator. Work shall be as herein specified and as denoted on the accompanying Drawings but not limited to the following general terms of work:
a. Storm sewers
b. Sanitary sewers
c. Catch basin and manholes
d. Trench drains
e. Oil/Water separators
2. Provide ______ gallon(s) aboveground steel oil/water separator tank(s), piping, necessary pumps, venting, vent piping, monitoring equipment, and oil draw-off pump(s) required to make a complete installation ready for use.
3. The separator shall be a pre-packaged, pre-engineered, ready to install unit.
4. The Contractor will provide filling of oil/water separator with clean water.
5. The Contractor shall mechanically unload the oil/water separator at the job site.
1.04 Governing Standards
1. National Fire Protection Assoc. (NFPA 30) Flammable and Combustible Liquids Code, (NFPA 30A) Automotive and Marine Service Station Code, (NFPA 70), National Electrical Code.
2. "Petroleum Equipment Institute Publication RP200-92; Recommended Practices for Installation of Aboveground Storage Systems for Motor Vehicle Fueling".
a. API manual on disposal of refinery wastes
b. API bulletin no. 421
c. API bulletin no. 1630 first edition (replaced by API 421)
d. Coast Guard Specification 46 CFR 162.50 - 46 CFR Chapter 1
e. EPA Test Method 413. 1, Oil and Grease, Total Recoverable (Gravimetric, Separatory Funnel Extraction).
f. EPA Test Method 413.2, Oil and Grease, Total Recoverable (Spectrophotometric, Infrared).
1.05 Quality Assurance
1. Test Data: The manufacturer must provide test data and a written report proving that the oil/water separator is capable of producing effluent with no more than 10 ppm free oil and grease (not dissolved nor chemically emulsified with soaps or detergents) when tested using the Coast Guard test method 46 CFR 162.50. The test inlet oils include both 0.8 and 0.9 specific gravity (approximate) oils.
2. Oil/Water separator tank shall be constructed to meet UL142 governing standards.
3. Shop Drawings: Contractor shall submit copies of shop drawings for each OWS tank. Drawings shall include all critical dimensions, locations of fittings and accessories.
4. All OWS tanks, equipment and piping materials shall be physically inspected and tested before being installed. Any defects observed shall be immediately brought to the attention of the Owner. It shall be the sole responsibility of the Contractor to correct any deficiencies, with the manufacturer in strict accordance with manufacturers' recommendations, at no additional cost to the Owner.
5. Contractor shall submit copies of manufacturer's literature.
6. Containment Solutions Oil/Water separators will not remove oils with specific gravities greater than 0.95, chemical or physical emulsions, dissolved hydrocarbons, or volatile organic compounds [VOC).
7. The contractor shall obtain and pay for all permits, tests, inspections, etc. required by the local boards that have jurisdiction over the project. All work shall be executed and inspected in accordance with all local and state codes, rules, ordinances, or regulations pertaining to the particular work involved. Should any changes in the contract drawings and specifications be required to conform to such ordinances, notify the owner at time of submitting bid. After entering into the contract the contractor shall be held responsible for the completion of all work necessary for a complete and approved installation without extra expense to the owner.
PART 2: PRODUCTS
2.01 Aboveground Horizontal Oil/Water Separators
Provide and install ________ Containment Solutions, Inc. ________ gallon capacity Model AOWS- ________ Oil/Water Separator. Separator shall be ________ long x ________ wide x ________ high.
1. Oil/Water Separator shall be designed in accordance with Stokes Law, and American Petroleum Institute (API) Publication 421, "Monographs on Refinery Environmental Control, Management of Waste Discharges, Design and Operation of Oil/Water Separators" to achieve an effluent quality of 10ppm.
2. Oil/Water Separator shall be manufactured and tested for leakage prior to shipment.
3. Oil/Water